Destined to be a workhorse of the industry, the Reliable Controls® MACH-Pro1 is a rugged, flexible and fully programmable BACnet Building Controller (B-BC) ideal for mid-sized rooftop equipment or small mechanical room applications.
Protocol
- BACnet®
– MS/TP and PTP
12 Inputs
- Universal ranges
- Jumper selectable 0-10 VDC, 4-20 mA, thermistor / dry contact
8 Outputs
- Universal ranges
- Optional HOA (Hand/Off/Auto) switches
- HOA position feedback to RC-Studio®
128 Variables
- Selectable standard and custom ranges, as well as fixed program-driven values
16 PID Loops
- Standard P, PI, or PID controllers for closed loop control
8 Schedules
- 14 On/Off times for each weekday or exception
4 Calendars
- Days of the year designated as holidays
10 Custom Tables
- For creating custom scaling functions
16 System Groups
- Allows related points to be grouped on to one display
- 80 points/group
16 Control-BASIC™ Programs
- User programmable control strategy in a readable, BASIC-like language
- 3200 bytes per program
Trend Logs
- Each Trend Log stores up to 8 points
- Values recorded at user-defined intervals
- Dynamically assigned
Runtime Logs
- Totals the On time and records the On/Off times of every binary point
- Holds 200 events
- Dynamically assigned
128 Variable Arrays
- Up to 128 elements in a one-dimensional array
128 User Passwords
- Protects access to system
- Each user is assigned a user name and an access level
24 Custom Units
- 8 analog engineering units
- 8 binary engineering units
- 8 multistate units
SMART-Net™ Port
- Networks up to 8 SMART-Sensors™
Real-Time Clock
Warranty
- 5 years
Certification
- BTL Listed (B-BC)
- UL916 Listed
- FCC CFR 47 Part 15/B
- CE
Processor
- 100 MHz, high-performance, 32-bit embedded microcontroller
Memory
- 8 MB operating RAM
- 1 MB non-volatile RAM
(trends and dynamic values) - 4 MB Flash EEPROM operating system, database, and controller configuration
Supply Voltages
- 24 VAC ±10% 75 VA max. 50/60 Hz
- 24 VDC ±10% 26 W max.
Communications
- 1 EIA-485 @ 76.8 kbps max.
Auto-baud detection - 1 EIA-232 @ 115.2 kbps max.
PC or modem - SMART-Net port @ 8 sensors max
Universal Inputs
- 12 universal inputs
- 12-bit A/D convertor
- Analog: 0-10 VDC, 4-20 mA, thermistor
- Binary: dry contact
- Impedance:
1M Ω for 0-10 VDC range
250 Ω for 4-20 mA range
20k Ω pull-up for thermistor/dry contact range - Pulse counting up to 150 Hz
(supports flow meters) - 24 VAC over-voltage protection
8 Outputs
- 12-bit D/A converter
- Analog: 0-12 VDC
- Binary: 0/12 VDC
- Manual ON provides adjustable 0-12 VDC (HOA model only)
- LED indicator (glows proportionally)
- Output power: 75 mA @ 12 VDC
- 24 VAC over-voltage and short protection
Peripheral Power
- Onboard variable 15-24 VDC power supply providing up to 200 mA of DC power to peripheral devices
(if powered by 24 VDC, the maximum voltage output is 22 VDC)
Real-Time Clock
- ±1 second per day
Memory/RTC Backup
- 72 hour backup
- 10 years for database
SETUP-Tool™
- SETUP-Tool optional for configuration
Dimensions
- 25.4 cm L x 13.7 cm W x 3.9 cm H
(10″ L x 5 3/8″ W x 1 1/2″ H)
Mounting
- #8 clearance holes on
23.0 cm L x 11.0 cm W
(9 1/16″ L x 4 5/16″ W) - Screw depth 25 mm (1″)
Weight
- 0.6 kg (1.3 lb)
Ambient Limits
- Operating: -20 ºC to 55 ºC
(-4 ºF to 131 ºF) - Shipping: -40 ºC to 60 ºC
(-40 ºF to 140 ºF) - Humidity: 10% to 90%
RH non-condensing