Small, durable and packed with flexibility, the Reliable Controls® MACH-ProZone™ is a fully programmable BACnet® Building Controller (B-BC) with highly scalable I/O in a very small footprint. The MACH-ProZone™ is ideal for a wide range of applications that include small to mid-sized roof top and heatpump applications, and small mechanical room applications.


      

 

Dynamic Database

  • Allows a maximum of 128 objects to be created of any supported type in any model of controller
  • Non-expanded memory models of MPZ-44, 48, and 84 provide 40K of database memory and 28K of trend memory
  • Typical Maximum Object Configuration table (below) shows the impact of base and expanded memory

Protocol

  • BACnet®
    – MS/TP (EIA-485)

Control-BASIC™ Programs

  • 8500 bytes programmable control strategy in a readable, BASIC-like language
  • 3200 bytes per program

Inputs

  • Universal ranges
  • Soft-selectable 0-10 VDC, 4-20 mA, thermistor / dry contact

Outputs

  • Universal ranges
  • Jumper selectable 0-12 VDC, or TRIAC

Variables

  • Selectable standard and custom ranges, as well as fixed or program-driven values

PID Loops

  • Standard P, PI, or PID controllers for closed loop control

Single-Point Trend Logs

  • Stores 128 samples at programmable time intervals

Multipoint Trend Logs

  • Each Trend Log stores 128 samples of 8 points at programmable time intervals

Runtime Report

  • Records the total On time and the total number of transitions, as well as daily transitions for every binary point
  • A 50 sample runtime log is optional for each binary point

System Groups

  • Allows related points to be grouped onto one display
  • 80 points/group

Schedules

  • 7 On/Off times for each weekday or exception

Calendars

  • Days of the year designated as holidays

Arrays

  • Up to 128 elements in a one-dimensional array

Tables

  • For creating custom input ranges and Control-BASIC™ lookup tables

Custom Units

  • 8 analog engineering units
  • 8 binary engineering units
  • 8 multistate units with 8 states, 32-characters each

SMART-Net™ Port

  • Networks up to 8 SMART-Sensors™

32 Network In Points (MPZ-44,48,84)
64 Network In Points (MPZ-88, and -XM)
16 Network Out Points (MPZ-44,48,84)

  • The total maximum number of writes and shares to other devices

32 Network Out Points (MPZ-88, and -XM)

  • The total maximum number of writes and shares to other devices

Warranty

  • 5 years

Certification

Typical Maximum Object Configuration
There are physical limitations to the number of inputs, outputs, and SMART-Sensors that can be connected to a MACH-ProZone. For other object types, there are no imposed limits for the maximum number of objects of a single type that can be created. The total number of objects (including inputs, outputs, and SMART-Sensors) is limited to 128, and is also limited by the onboard memory. The table below details typical databases that fit in the Base and Expanded memory models.

Memory* Variables Loops Schedules Calendars Tables** Groups Multipoint Trend Runtime** Arrays Program SMART-Sensor
Base 48 4 2 1 2 2 2 32 2 8 4
Expanded 64 8 4 2 4 4 10 128 4 8 8

* MPZ-44, 48, and 84 ship with base memory – MPZ-88 and -XM models ship with expanded memory
** Tables and Runtime Logs are not counted in the 128 object limit. Inputs, outputs, and the device object are counted in the 128 object limit.
*** All models accommodate a maximum of 8 SMART-Sensors

Processor & Memory

  • 66 MHz, high performance, 32-bit embedded microcontroller with onboard Flash memory
  • Controller database, values and configuration held in robust non-volatile memory
  • Operating System firmware easily updated at any time over the network

Supply Voltages

  • 24 VAC ±10% 25 VA max. 50/60 Hz
  • 24 VDC ±10% 12 W max.

Communications

  • EIA-485 @ 76.8 kbps max.
  • SMART-Net™ (8 SMART-Sensors™ max.)
  • Auto-baud detection

Universal Inputs

  • 12-bit A/D converter
  • Soft selectable: 0-10 VDC, 4-20 mA, thermistor/dry contact
  • Impedance:
    3M O on 0-10 VDC range
    250 O on 4-20 mA range
    20k O on thermistor range
  • Pulse counting up to 40 Hz (supports flow meters)
  • 24 VAC over-voltage protection

Universal Outputs

  • 12-bit D/A converter
  • Analog: 0-12 VDC
  • Binary: 0/12 VDC
  • Output power: 75 mA @ 12 VDC
  • 24 VAC over-voltage and short protection
  • Jumper selectable TRIAC

TRIAC Outputs

  • 24 VAC @ 1 A

SETUP-Tool™

  • SETUP-Tool™ optional for configuration

Dimensions
10.9 cm L x 19.1 cm W x 4.9 cm H
(4 5/16″ L x 7 1/2″ W x 1 5/16″ H)

Mounting

  • DIN rail, or
  • #8 clearance holes on 17.8 cm W (7″ W) centerline

Weight

  • 0.3 kg (0.7 lb.)Ambient Limits
    • Operating: -20 ºC to 55 ºC
      (-4 ºF to 131 ºF)
    • Shipping: -40 ºC to 60 ºC
      (-40 ºF to 140 ºF)
    • Humidity: 10% to 90%
      RH non-condensing