Take ownership of your personal environment with the Reliable Controls® SMART-Space Controller™ (SSC), a fully programmable BACnet controller with multi-sensor capability and ten-point, on screen direct control.
Aesthetic Design
- Smooth contour lines
- Slim profile
Protocol
- BACnet MS/TP Slave
4 Control-BASIC™ Programs
- User programmable control strategy in a readable, BASIC-like language
- 2000 bytes per program
Up to 4 Inputs
- 3 universal, and 1 dedicated temperature sensor
- Jumper selectable 0-10 VDC, 4-20 mA, thermistor/dry contact
Up to 4 Outputs
- Jumper selectable to be universal or TRIAC
- Universal supplies 0-12 VDC, 20mA @ 12-bit DAC
- Relay switches 24 VAC/VDC @ 0.5A
32 Variables
- Selectable standard and custom ranges, as well as fixed or program-driven values
2 PID Loops
- Standard P, PI, or PID controllers for closed loop control
2 BACnet Trend Log Multiple
- Capable of storing program-timed or runtime-triggered values
- Up to 8 points per trend
1 System Group
- Allows related points to be grouped on to one display
- 30 points per group
1 BACnet Schedule
- 4 time value pairs for each weekday
- 8 special events
2 Custom Tables
- For creating custom input ranges and Control-BASIC lookup tables
LCD
- Displays up to 10 points
- Adjustable backlight timeout
Warranty
- 5 years
- 1 year for humidity and CO2 sensor
Certification
- BTL Listed (B-Gen)
- FCC CFR 47 Part 15/B
- CE
Supply Voltages
- 24 VAC/VDC ± 15%
- 10 VA (SSC, SCCE)
- 65 VA (SSCP, including relay outputs)
Display
- Four 0.6″ digits
- Six 0.3″ characters
- Eleven icons: Auto, On, Off, Cool, Occupied, Heat, Fan, Fan Speed, AM, PM, and Day of the Week
- Backlit for easy viewing in dim light
- Display Area 36mm x 36mm (1 3/8″ x 1 3/8″)
Temperature Specifications
- 12-bit A/D converter
- Range: 0ºC to 40ºC (32ºF to 104ºF)
- ±0.1ºC (0.18ºF) resolution
- User calibrated to ±0.1ºC (0.18ºF) accuracy
Humidity Sensor (for -H models)
- 0.1% resolution
- 10-90% range
- ±1.8% RH accuracy
Occupancy Sensor (for -OC models)
- Passive Infrared Radiation (PIR) sensor
- 64 detection zones
- 100º horizontal range / 82º vertical range
- 5 m (16.4 ft.) detection distance
Buttons
- 3 custom silicon rubber buttons
- Button functions: select, plus, and minus
CO2 Sensors (for -CO2 models)
- Non Dispersive Infrared Optical Sensor
- 0-2000 ppm range
- Accuracy ±50 ppm
- Automatic calibration built in
- Non Linearity < 1% of full scale
- Power: adds 2 mA to the base SSC
X-Port-2
- Access port for PC connection using X-Port-2™ converter
Communications
- MS/TP BACnet slave @ 76800 baud max with AutoBaud
- Up to 200 SSCs per network
Inputs
- 12-bit A/D convertor
- Up to 4 Inputs (3 universal, and 1 dedicated temperature sensor)
- Jumper selectable 0-10 VDC, 4-20 mA, thermistor / dry contact
Outputs
- Up to 4 outputs (combination of universal and TRIAC)
- Universal supplies 12 VDC 20 mA @ 12-bit DAC
- Relay switches 24 VAC/VDC @ 0.5 A
.
Real-Time Clock (optional)
- ±1 second per day
Memory/RTC Backup
- 72 hour backup
- 10 years for database
Dimensions
- 16 to 24 AWG (1.31 mm2 to 0.21 mm2)
- Stranded or solid core
- Copper conductors only
Dimensions
- 12 cm L x 7.0 cm W x 3.2 cm H (4 3/4″ L x 2 3/4″ W x 1 1/4″ H)
Weight
- 0.13 kg (0.287 lb.)
Ambient Limits
- Operating: -20 ºC to 55 ºC
(-4 ºF to 131 ºF) - Shipping: -40 ºC to 60 ºC
(-40 ºF to 140 ºF) - Humidity: 10% to 90% RH non-condensing