A complement to any room, the Reliable Controls® SMART-Sensor™ (SS) is a very versatile room sensor that communicates digitally, saving hard inputs in the host controller.
Aesthetic Design
- Smooth contoured lines
- Slim profile
Easy Programming
- Simply drag and drop points from the host controller onto the SS worksheet to configure
Connection & Addressing
- Configure network address of SS using 4 pole DIP switch
- Valid addresses are 1-16
- Four wire connection to SS-P
- Four or six wire connection to SS
(six wire required for use with X-Port-2™)
Network Access
- An RJ-11 connector on the bottom provides access to the host network
(X-Port-2 required; not available on -S, -P models)
Optional CO2
- 0-2000 ppm ±50 ppm NDIR sensor
Optional Humidity
- Accurate onboard humidity sensor
Optional I/O
- Up to 2 thermistor or dry contact inputs, and up to 2 digital TRIAC outputs
Optional Override Button
- Use to override unoccupied mode
Optional Occupancy
- Extremely compact sensor, ideal for detecting the motion of a person up to 5 m (16 ft.) away
Optional Setpoint Slider
- Linear potentiometer with warm/cool decal
Optional Up/Down Buttons
- Use up/down buttons to adjust setpoint
Plate Model
- Mounts to a standard single electrical device box
Warranty
- 5 years
- 1 year for humidity sensor and CO2 sensor
Certification
- FCC CFR 47 Part 15/B
Supply Voltages (from controller)
- SS – 5 VDC @ 5 mA
- -IO option adds 10 mA
- -CO2 option adds 2 mA
- -OC option adds 0.2 mA
Temperature Specifications
- 12-bit A/D converter
- User calibrated to ± 0.1 °C (0.18 °F) accuracy
- Range, SS: -40 °C to 40 °C (-40 °F to 185 °F)
- Range, SS-IO: -40 °C to 120 °C
(-40 °F to 250 °F) - Range, SS-P: 0 °C to 50 °C (32 °F to 122 °F)
CO2 Sensor (for -CO2 models)
- Non Dispersive Infrared Optical sensor
- 0-2000 ppm range
- Accuracy ±50 ppm
- Automatic calibration built in
- Non Linearity < 1% of full scale
- Power: adds 2 mA to the base SS
Humidity Range (for -H models)
- 10-90% range
- ± 1.8% RH accuracy
Inputs
- Dedicated temperature sensor
- 2 thermistor or dry contact (on -IO models)
Outputs (for -IO models)
- 2 on/off TRIAC
- 24 VAC @ 0.5 A
Occupancy Sensor (for -OC models)
- Passive Infrared Radiation (PIR) sensor
- 64 detection zones
- 100° horizontal range / 82° vertical range
- 5 m (16.4 ft.) max. detection distance
Buttons
- 2 custom silicon rubber buttons for up/down adjust (-UD model)
- UD buttons not available on model with setpoint slider (-S model)
- 1 custom silicon rubber button for override
(-O model) - 1 custom brass button for override (-P-O model)
Wiring Terminals
- 14 to 26AWG (2.08 mm² to 0.13 mm²)
- Stranded or solid core
- Copper conductors only
Dimensions
Base model:
- 12 cm L x 7 cm W x 2.4 cm H
(4 3/4″ L x 2 3/4″ W x 15/16″ H)
CO2 model: - 12 cm L x 7 cm W x 3.2 cm H
(4 3/4″ L x 2 3/4″ W x 1 1/4″ H)
Plate Model: - 11.4 cm L x 7 cm W x 3.6 cm H
(4 1/2″ L x 2 3/4″ W x 1 3/8″ H)
Weight
- SS: 0.086 kg (0.19 lb.)
- SS-P: 0.073 kg (0.16 lb.)
Ambient Limits
SS:
- Operating: -40 °C to 40 °C (-40 °F to 104 °F)
- Shipping: -40 °C to 60 °C (-40 °F to 140 °F)
SS-P: - Operating: 0 °C to 50 °C (32 °F to 122 °F)
- Shipping: 0 °C to 50 °C (32 °F to 122 °F)
SMART-Sensor eXpansion
The SSX is used when mulitple SMART-Sensors (SSs) are to be connected to one controller’s SMART-Net port.